The senTemIn.T trace covers 20.344 to 30 °C, a temperature span of 9.656 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named FlowReversal. The source file places it under Fluid, Fixed Resistances, Plug Flow Pipes. We used the 101 stored values for senTemIn.T over the interval 0 to 150 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name m_flow (Step), sin (Boundary p T), pip (Plug Flow Pipe), sou (Mass Flow Source T). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTemOut.T covers 293.15 to 313.15 K. At 150 s, the primary value is 293.494 and the companion is 313.15. Their signed difference is -19.656 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Plug flow pipe with flow reversal. The simulated senTemIn.T channel runs from 293.494 to 303.15 K over 150 seconds.
Plug flow pipe with flow reversal. The simulated senTemIn.T channel runs from 293.494 to 303.15 K over 150 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 49.5 to 51 seconds. Subtracting 303.15 from 302.457 gives -0.6929 K. Its location brackets the change within one saved interval of 1.5 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTemIn.T (K)

senTemOut.T (K)

0

303.15

293.15

30

303.15

293.15

49.5

303.15

293.15

51

302.4571

313.15

60

302.3569

313.15

90

300.178

313.15

120

294.8598

313.15

150

293.4944

313.15

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.