The plug-flow pipe outlet temperature starts at 50 °C and finishes at 69.969 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 49.982 °C and 69.969 °C.

What the reference test measures

The Buildings model named PlugFlowPipeDiscretized comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 1,000 seconds. Industry Applied extracted 101 checkpoints for senTemOut.T and kept the original signed values. The regular output spacing is 10 seconds. The solver may take different internal steps.

The model definition identifies senTemOut (Temperature Two Port), senTemIn (Temperature Two Port), Tin (Ramp). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares Tin.height = 20, Tin.duration = 0, Tin.startTime = 100. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 110 seconds, senTemOut.T is 323.132 and senTemIn.T is 343.15. Subtracting the second channel from the first gives -20.018 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Plug-flow pipe outlet temperature. In the simulated PlugFlowPipeDiscretized case, senTemOut.T ranges from 323.132 to 343.119 K over 1,000 seconds.
Plug-flow pipe outlet temperature. In the simulated PlugFlowPipeDiscretized case, senTemOut.T ranges from 323.132 to 343.119 K over 1,000 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 180 and 190 seconds, senTemOut.T changes from 323.133 to 343.119. Subtracting the earlier reading gives +19.986 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

senTemOut.T (K)

senTemIn.T (K)

0

323.15

323.15

90

323.1316

323.15

180

323.1326

343.15

190

343.1187

343.15

200

343.1189

343.15

250

343.1189

343.15

500

343.1189

343.15

750

343.1189

343.15

1000

343.1189

343.15

Applying the result to an operating site

A temperature front needs time to traverse the pipe while exchanging heat with its surroundings. Flow, water volume and insulation influence the result. Distinguish this transport effect from the thermal lag of the outlet sensor.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.

Cover photograph by Jakub Zerdzicki, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.