The senTemOut.T trace covers 49.923 to 69.879 °C, a temperature span of 19.956 K. The first recorded maximum occurs at 720 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named StaticPipe. The source file places it under Fluid, District Heating Cooling, Pipes. We used the 101 stored values for senTemOut.T over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name Tin (Ramp), sin (Boundary p T), pip (Static Pipe), bou (Fixed Temperature). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel senTemIn.T covers 323.15 to 343.15 K. At 110 s, the primary value is 328.131 and the companion is 343.15. Their signed difference is -15.019 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 100 to 110 seconds. Subtracting 323.073 from 328.131 gives 5.058 K. Its location brackets the change within one saved interval of 10 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | senTemOut.T (K) | senTemIn.T (K) |
|---|---|---|
0 | 323.15 | 323.15 |
100 | 323.0732 | 323.15 |
110 | 328.1314 | 343.15 |
200 | 342.0495 | 343.15 |
400 | 343.0265 | 343.15 |
600 | 343.0288 | 343.15 |
720 | 343.0288 | 343.15 |
800 | 343.0288 | 343.15 |
1000 | 343.0288 | 343.15 |
What to check on site
Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.