The phase-change layer temperature starts at 20 °C and finishes at 20.62 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 20 °C and 20.62 °C.
What the reference test measures
The Buildings model named ConductorSingleLayerPCM comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 7,200 seconds. Industry Applied extracted 101 checkpoints for conPCM.T[2] and kept the original signed values. The regular output spacing is 72 seconds. The solver may take different internal steps.
The model definition identifies conPCM (Single Layer), con1 (Single Layer), TA (Prescribed Temperature). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Reading the two channels
At 0 seconds, conPCM.T[2] is 293.15 and con1.T[2] is 293.15. Subtracting the second channel from the first gives 0 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.
![Phase-change layer temperature. In the simulated ConductorSingleLayerPCM case, conPCM.T[2] ranges from 293.15 to 293.77 K over 7,200 seconds.](https://static.wixstatic.com/media/21e41b_2931cc50d4fd48a6adb476a814aef091~mv2.png/v1/fill/w_616,h_345,al_c,q_85,enc_auto/21e41b_2931cc50d4fd48a6adb476a814aef091~mv2.png)
Reproducing the largest recorded change
Between the stored points at 4,104 and 4,176 seconds, conPCM.T[2] changes from 293.449 to 293.456. Subtracting the earlier reading gives +0.007721 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | conPCM.T[2] (K) | con1.T[2] (K) |
|---|---|---|
0 | 293.15 | 293.15 |
1800 | 293.2196 | 293.2196 |
3600 | 293.3948 | 293.3948 |
4104 | 293.4485 | 293.4485 |
4176 | 293.4562 | 293.4562 |
5400 | 293.5865 | 293.5865 |
7200 | 293.7704 | 293.7704 |
Applying the result to an operating site
A phase transition can absorb or release energy across a narrow temperature range. A flat temperature period does not by itself measure stored latent heat. Compare boundary heat flows and the initial phase condition alongside the temperature trace.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.