The setPoiVAV.y trace ranges from 0.3 to 0.9 across 101 saved checkpoints. It begins at 0.9 and finishes at 0.3 after 3,600 s of test time. The source identifies the channel scale as dimensionless. Its first saved maximum occurs at 0 s.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Supply_T. The source file places it under Controls, OBC, ASHRAE, G36, AH Us, Single Zone, variable air volume, Set Points. We used the 101 stored values for setPoiVAV.y over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name setPoiVAV (Supply), uHea (Constant), uCoo (Constant), TOut (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 43.6% of its saved checkpoints at or above 0.6 source units, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 0.56 source units. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Outdoor minus room air temperature. The simulated setPoiVAV.y channel runs from 0.3 to 0.9 source units over 3,600 seconds.
Outdoor minus room air temperature. The simulated setPoiVAV.y channel runs from 0.3 to 0.9 source units over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 1,728 to 1,764 seconds. Subtracting 0.432 from 0.396 gives -0.036 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

setPoiVAV.y (dimensionless)

0

0.9

720

0.9

1440

0.7189059

1728

0.4319931

1764

0.3959967

2160

0.3001477

2880

0.3

3096

0.2999994

3600

0.3

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, setPoiVAV.y uses dimensionless. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.