The zonAHUG36Con.TZon trace covers 17.029 to 20.515 °C, a temperature span of 3.486 K. The first recorded maximum occurs at 60,480 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Guideline36Winter. The source file places it under Air, Systems, Single Zone, variable air volume, Optimal Start. We used the 101 stored values for zonAHUG36Con.TZon over the interval 0 to 604,800 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 6 recorded variables. Alongside the primary output there are zonAHUG36Con.con.TZonHeaSet, zonAHUG36Con.con.TZonCooSet, zonAHUG36Opt.TZon, zonAHUG36Con.TZon, optStaHea.tOpt. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel zonAHUG36Opt.TZon covers 290.686 to 293.724 K. At 544,320 s, the primary value is 290.179 and the companion is 292.844. Their signed difference is -2.665 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Optimal start guideline36 winter. The simulated zonAHUG36Con.TZon channel runs from 290.179 to 293.665 K over 604,800 seconds.
Optimal start guideline36 winter. The simulated zonAHUG36Con.TZon channel runs from 290.179 to 293.665 K over 604,800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 459,648 to 465,696 seconds. Subtracting 290.781 from 292.937 gives 2.156 K. Its location brackets the change within one saved interval of 6,048 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

zonAHUG36Con.TZon (K)

zonAHUG36Opt.TZon (K)

0

293.15

293.15

60480

293.6652

293.7239

120960

293.166

293.2728

241920

292.2657

292.3726

362880

290.9695

291.0938

459648

290.7809

292.874

465696

292.9373

293.3863

483840

293.219

293.1919

544320

290.1791

292.8442

604800

291.2706

291.5841

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.