The zonAHUG36Con.TZon trace covers 19.165 to 23.9 °C, a temperature span of 4.734 K. The first recorded maximum occurs at 6,883,488 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named Guideline36Spring. The source file places it under Air, Systems, Single Zone, variable air volume, Optimal Start. We used the 101 stored values for zonAHUG36Con.TZon over the interval 6,393,600 to 7,171,200 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name weaDat (Reader TMY3), optStaHea (Optimal Start), occSch (Occupancy Schedule), TSetHeaOn (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel zonAHUG36Opt.TZon covers 292.315 to 297.064 K. At 6,424,704 s, the primary value is 293.073 and the companion is 293.253. Their signed difference is -0.1797 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 6,595,776 to 6,603,552 seconds. Subtracting 292.992 from 294.134 gives 1.142 K. Its location brackets the change within one saved interval of 7,776 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | zonAHUG36Con.TZon (K) | zonAHUG36Opt.TZon (K) |
|---|---|---|
6393600 | 293.15 | 293.15 |
6416928 | 292.3155 | 292.3155 |
6549120 | 293.5995 | 293.6233 |
6595776 | 292.992 | 293.0132 |
6603552 | 294.1339 | 294.1554 |
6704640 | 295.843 | 295.8618 |
6860160 | 295.8749 | 295.8895 |
6883488 | 297.0497 | 297.0641 |
7015680 | 295.8347 | 295.8477 |
7171200 | 295.2584 | 295.269 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.