The recorded optSta.TZon temperature spans 18.888 °C to 26.156 °C in this simulation. That is a change of 7.2688 K. The first saved maximum occurs at 798,336 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named OptimalStartNoHeatingNoCooling. The source file places it under Controls, OBC, Utilities. We used the 101 stored values for optSta.TZon over the interval 0 to 2,419,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name optSta (Optimal Start), TRoo (Integrator), TOutBase (Sin), UA (Multiply By Parameter). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 628,992 s, optSta.TZon reads 295.699 K and TSetCoo.y reads 303.15. Across the run, the second channel ranges from 297.15 to 303.15. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Optimal start for the case with no preheating nor precooling. The simulated optSta.TZon channel runs from 292.038 to 299.306 K over 2,419,200 seconds.
Optimal start for the case with no preheating nor precooling. The simulated optSta.TZon channel runs from 292.038 to 299.306 K over 2,419,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 604,800 to 628,992 seconds. Subtracting 292.708 from 295.699 gives 2.991 K. Its location brackets the change within one saved interval of 24,192 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

optSta.TZon (K)

TSetCoo.y (source units)

0

292.15

303.15

24192

292.0377

303.15

483840

294.15

297.15

604800

292.7076

303.15

628992

295.6985

303.15

798336

299.3065

303.15

967680

298.999

303.15

1451520

294.0726

303.15

1935360

297.15

297.15

2419200

297.6843

303.15

What to check on site

Compare fuel or electrical input with useful heat at a declared delivery boundary. Include the warm-up interval and any period on standby. Separate a temperature setpoint from the measured outlet and keep auxiliary energy in a stated part of the balance.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.