The zonAHUCon.TZon trace covers 20 to 25.844 °C, a temperature span of 5.844 K. The first recorded maximum occurs at 16,746,048 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ConventionalSummer. The source file places it under Air, Systems, Single Zone, variable air volume, Optimal Start. We used the 101 stored values for zonAHUCon.TZon over the interval 15,984,000 to 16,761,600 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 5 recorded variables. Alongside the primary output there are TSetRooHea.y[1], TSetRooCoo.y[1], zonAHUOpt.TZon, zonAHUCon.TZon, optSta.tOpt. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel zonAHUOpt.TZon covers 293.15 to 298.972 K. At 16,271,712 s, the primary value is 298.254 and the companion is 297.425. Their signed difference is 0.8283 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Optimal start conventional summer. The simulated zonAHUCon.TZon channel runs from 293.15 to 298.994 K over 777,600 seconds.
Optimal start conventional summer. The simulated zonAHUCon.TZon channel runs from 293.15 to 298.994 K over 777,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 16,738,272 to 16,746,048 seconds. Subtracting 297.086 from 298.994 gives 1.909 K. Its location brackets the change within one saved interval of 7,776 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

zonAHUCon.TZon (K)

zonAHUOpt.TZon (K)

1.5984e+07

293.15

293.15

1.613952e+07

298.0889

298.0889

1.629504e+07

297.1708

297.1718

1.645056e+07

297.3344

297.3221

1.660608e+07

298.318

298.3057

1.673827e+07

297.0858

297.0881

1.674605e+07

298.9944

298.9721

1.67616e+07

298.7062

298.6834

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.