The zonAHUCon.TZon trace covers 19.165 to 22.836 °C, a temperature span of 3.67 K. The first recorded maximum occurs at 6,883,488 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ConventionalSpring. The source file places it under Air, Systems, Single Zone, variable air volume, Optimal Start. We used the 101 stored values for zonAHUCon.TZon over the interval 6,393,600 to 7,171,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name weaDat (Reader TMY3), optSta (Optimal Start), occSch (Occupancy Schedule), TSetHeaOn (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel zonAHUOpt.TZon covers 292.315 to 296.008 K. At 6,595,776 s, the primary value is 292.552 and the companion is 293.225. Their signed difference is -0.6728 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Optimal start conventional spring. The simulated zonAHUCon.TZon channel runs from 292.315 to 295.986 K over 777,600 seconds.
Optimal start conventional spring. The simulated zonAHUCon.TZon channel runs from 292.315 to 295.986 K over 777,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 6,416,928 to 6,424,704 seconds. Subtracting 292.315 from 293.306 gives 0.9908 K. Its location brackets the change within one saved interval of 7,776 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

zonAHUCon.TZon (K)

zonAHUOpt.TZon (K)

6393600

293.15

293.15

6416928

292.3155

292.3155

6424704

293.3063

293.3598

6549120

293.2426

293.2677

6704640

295.221

295.25

6860160

294.7542

294.7783

6883488

295.9855

296.0079

7015680

294.9827

295.0035

7171200

294.1943

294.2118

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.