The recorded demand.port_a.m_flow channel spans 0.2007 to 0.5646 kg/s in this reference run. It starts at 0.3826 and ends at 0.3826. The first recorded maximum occurs at 2,000 seconds and the first minimum at 58,000 seconds.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named OpenLoopVarTSupplyDpFixedTempDifferenceBypass. The source file places it under Fluid, District Heating Cooling, Demands. We used the 101 stored values for demand.port_a.m_flow over the interval 0 to 100,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name sourceIdeal (Source Ideal), demand (Var T Supply pressure difference Fixed Temp Difference Bypass), pipeSupply (Plug Flow Pipe), pipeReturn (Plug Flow Pipe). The source declares T_amb = 283.15. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The primary channel spends 39.6% of its saved checkpoints at or above 0.3826 kg/s, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 0.3826 kg/s. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Reproduce the calculation
Integrating the signed rate over 100,000 seconds gives a net 38,262 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | demand.port_a.m_flow (kg/s) |
|---|---|
0 | 0.3826238 |
2000 | 0.5645722 |
20000 | 0.3826238 |
40000 | 0.3826238 |
54000 | 0.4950741 |
55000 | 0.3826238 |
58000 | 0.2006754 |
60000 | 0.3826238 |
80000 | 0.3826238 |
100000 | 0.3826238 |
What to check on site
Trace the transfer boundary between the central network and the local load. Identical terminal duty can coincide with different distribution losses and pump inputs. Use simultaneous primary and secondary measurements before allocating an energy difference to one side.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.