The pum.P series gives a net 0.27998 kWh over 172,800 s when the saved power samples are joined by straight lines. The highest recorded power is 10.324 W. The sign follows the model’s measurement boundary. It matters when a connector can exchange energy in either direction.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named HeatPumpRadiantHeatingGroundHeatTransfer. The source file places it under Thermal Zones, Energy Plus 24 2 0, Single Family House. We used the 101 stored values for pum.P over the interval 0 to 172,800 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name livFlo (Zone Surface), slaFlo (Parallel Circuits Slab), pre (Boundary ph), preHeaLivFlo (Prescribed Heat Flow). The source declares QHea_flow_nominal = 8000. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 17,280 s, pum.P is 10.324 W and heaPum.P is 2,072.6 W. Subtracting the second value from the first gives -2,062.2 W. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
Integrating the signed pum.P samples by the trapezoidal rule gives 0.28 kWh over 172,800 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | pum.P (W) | heaPum.P (W) |
|---|---|---|
0 | 0 | 0 |
1728 | 10.32388 | 1952.978 |
34560 | 0 | 0 |
69120 | 10.32388 | 1076.272 |
103680 | 10.32388 | 581.8886 |
115776 | 0 | 0 |
138240 | 0 | 0 |
172800 | 10.32388 | 1157.109 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.