The recorded terAutoSize[1].port_aHeaWat.m_flow channel spans 0.1087 to 0.4625 kg/s in this reference run. It starts at 0.1087 and ends at 0.2374. The first recorded maximum occurs at 72 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Distribution1PipeExample. The source file places it under DHC, Networks. We used the 101 stored values for terAutoSize[1].port_aHeaWat.m_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name loa (Combi Time Table), minTSet (Constant), reaRep (Real Scalar Replicator), reaRep1 (Real Scalar Replicator). The source declares filNam = , nLoa = 5, T_aHeaWat_nominal = 273.15 + 40, T_aLoaHea_nominal = 273.15 + 20. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel terPlugFlow[1].port_aHeaWat.m_flow covers 0.1087 to 0.3772 kg/s. At 108 s, the primary value is 0.4434 and the companion is 0.3469. Their signed difference is 0.09647 kg/s, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Networks distribution1 pipe. The simulated terAutoSize[1].port_aHeaWat.m_flow channel runs from 0.1087 to 0.4625 kg/s over 3,600 seconds.
Networks distribution1 pipe. The simulated terAutoSize[1].port_aHeaWat.m_flow channel runs from 0.1087 to 0.4625 kg/s over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 3,600 seconds gives a net 904.409 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

terAutoSize[1].port_aHeaWat.m_flow (kg/s)

terPlugFlow[1].port_aHeaWat.m_flow (kg/s)

0

0.1087294

0.1087294

36

0.3792578

0.3401928

72

0.4624961

0.3771823

720

0.2463105

0.2460106

1440

0.2430844

0.2430941

2160

0.2403034

0.2403155

2880

0.2382136

0.238227

3600

0.2373652

0.2373795

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.