The recorded pow_1dat.V_flow channel spans -5.28e-05 to 5.28e-05 m³/s in this reference run. It starts at 5.28e-05 and ends at -5.28e-05. The first recorded maximum occurs at 0 seconds and the first minimum at 0.75 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named PowerLaw. The source file places it under Airflow, Multizone. We used the 101 stored values for pow_1dat.V_flow over the interval 0 to 1 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name pow_m_flow (Coefficient m flow), roo1 (Boundary p T), roo2 (Boundary p T), ramp1 (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel pow_2dat.V_flow covers -5.3e-05 to 5.3e-05 m³/s. At 0 s, the primary value is 5.28e-05 and the companion is 5.3e-05. Their signed difference is -2.1e-07 m³/s, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Multizone powerlaw. The simulated pow_1dat.V_flow channel runs from -5.28e-05 to 5.28e-05 m³/s over 1 seconds.
Multizone powerlaw. The simulated pow_1dat.V_flow channel runs from -5.28e-05 to 5.28e-05 m³/s over 1 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 1 seconds gives a net 0 m³. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

pow_1dat.V_flow (m³/s)

pow_2dat.V_flow (m³/s)

0

5.282101e-05

5.303068e-05

0.2

5.282101e-05

5.303068e-05

0.4

3.076254e-05

3.092452e-05

0.49

7.907193e-06

7.974643e-06

0.5

0

0

0.6

-3.076253e-05

-3.092451e-05

0.75

-5.282101e-05

-5.303068e-05

0.8

-5.282101e-05

-5.303068e-05

1

-5.282101e-05

-5.303068e-05

What to check on site

Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model