The recorded pum.P channel spans 0 to 453.012 W in this reference run. It starts at 0 and ends at 453.012. The first recorded maximum occurs at 510 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named MultiplePumpsSpeed. The source file places it under DHC, Plants, Combined, Subsystems. We used the 101 stored values for pum.P over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name spe (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senMasFlo.m_flow starts at 0, ends at 1.92 and has a recorded range of 0 to 1.92 kg/s. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Multiple pumps model with speed-controlled pump. The simulated pum.P channel runs from 0 to 453.012 W over 1,000 seconds.
Multiple pumps model with speed-controlled pump. The simulated pum.P channel runs from 0 to 453.012 W over 1,000 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed pum.P samples by the trapezoidal rule gives 0.07847 kWh over 1,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

pum.P (W)

senMasFlo.m_flow (kg/s)

0

0

0

200

57.99487

0.1530156

400

133.261

1.093663

410

275.0565

1.424943

510

453.0124

1.919959

600

453.0124

1.919959

800

453.0124

1.919959

1000

453.0124

1.919959

What to check on site

Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.