The recorded mulSpeDX.P channel spans 0 to 9,108 W in this reference run. It starts at 0 and ends at 6,324. The first recorded maximum occurs at 1,836 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named MultiStage. The source file places it under Fluid, direct expansion Systems, Cooling, Water Source. We used the 101 stored values for mulSpeDX.P over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sinAir (Boundary p T), souAir (Mass Flow Source T), TEvaIn (Ramp), mulSpeDX (Multi Stage). The source declares dpEva_nominal = 1000, dpCon_nominal = 40000. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel mulSpeDX.eva.dxCoi.Q_flow starts at 0, ends at -20,199 and has a recorded range of -29,715 to 0 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Multi speed water source direct expansion coil. The simulated mulSpeDX.P channel runs from 0 to 9,108 W over 3,600 seconds.
Multi speed water source direct expansion coil. The simulated mulSpeDX.P channel runs from 0 to 9,108 W over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed mulSpeDX.P samples by the trapezoidal rule gives 4.736 kWh over 3,600 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

mulSpeDX.P (W)

mulSpeDX.eva.dxCoi.Q_flow (W)

0

0

0

720

0

0

1440

3643.347

-11886.19

1800

3643.347

-11886.19

1836

9108.367

-29715.48

2160

9108.367

-29715.48

2880

6333.289

-20300.89

3600

6323.852

-20198.79

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.