The published valLin.phi signal spans 0.05 to 1 fraction of one in the reference run. It starts at 0.525 and finishes at 0.349. The signed change between those endpoint samples is -0.176 fraction of one.

What the reference test measures

The Buildings model named TwoWayValvesMotor comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 600 seconds. Industry Applied extracted 101 checkpoints for valLin.phi and kept the original signed values. The regular output spacing is 6 seconds. The solver may take different internal steps.

The model definition identifies valLin (Two Way Linear), valEqu (Two Way Equal Percentage), sou (Boundary p T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares valLin.m_flow_nominal = 2, sou.T = 293.15, sin.T = 293.15. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 450 seconds, valLin.phi is 0.636 and valEqu.phi is 0.414. Subtracting the second channel from the first gives +0.222 fraction of one, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Motorised valve coefficient. In the simulated TwoWayValvesMotor case, valLin.phi ranges from 0.05 to 1 fraction of one over 600 seconds.
Motorised valve coefficient. In the simulated TwoWayValvesMotor case, valLin.phi ranges from 0.05 to 1 fraction of one over 600 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 90 and 96 seconds, valLin.phi changes from 0.525 to 0.62. Subtracting the earlier reading gives +0.095 fraction of one. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

valLin.phi (fraction)

valEqu.phi (fraction)

0

0.525

0.3162278

30

0.05

0.05

90

0.525

0.3162278

96

0.62

0.3981072

120

1

1

150

0.81

0.6309574

300

0.05

0.05

450

0.6358333

0.413682

600

0.3485714

0.2061986

Applying the result to an operating site

A motor’s travel time and the valve’s characteristic describe different mechanisms. Compare coefficient at the same stem position, then repeat the comparison over elapsed time. Position feedback, where available, separates a slow actuator from a nonlinear valve.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.