The recorded ctrBasic.registerBus.TAirInMea channel spans 283.15 to 293.15 source units in this reference run. It starts at 293.15 and ends at 283.15. The first recorded maximum occurs at 0 seconds and the first minimum at 216 seconds.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named Heater. The source file places it under Systems, Modular air handler. We used the 101 stored values for ctrBasic.registerBus.TAirInMea over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 3 recorded variables. Alongside the primary output there are ctrBasic.registerBus.TAirInMea, ctrBasic.registerBus.TAirOutMea, ctrBasic.registerBus.hydraulicBus.valveSet. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel ctrBasic.registerBus.TAirOutMea covers 284.823 to 293.15 source units. At 3,276 s, the primary value is 283.15 and the companion is 293.15. Their signed difference is -10 source units, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Modular air handler heating register. The simulated ctrBasic.registerBus.TAirInMea channel runs from 283.15 to 293.15 source units over 3,600 seconds.
Modular air handler heating register. The simulated ctrBasic.registerBus.TAirInMea channel runs from 283.15 to 293.15 source units over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 36 seconds. Subtracting 293.15 from 284.06 gives -9.09 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

ctrBasic.registerBus.TAirInMea (source units)

ctrBasic.registerBus.TAirOutMea (source units)

0

293.15

293.15

36

284.0597

285.8082

216

283.15

289.3074

720

283.15

292.7602

1440

283.15

293.1272

2160

283.15

293.1486

2880

283.15

293.1499

3600

283.15

293.15

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.