The published mov1.P signal spans 0 to 22,830.26 W in the reference run. It starts at 0 and finishes at 13,185.326. The signed change between those endpoint samples is +13,185.326 W.
What the reference test measures
The AixLib model named ComparePowerInput comes from the RWTH Aachen University E.ON Energy Research Center. The saved result covers simulation time 0 to 200 seconds. Industry Applied extracted 101 checkpoints for mov1.P and kept the original signed values. The regular output spacing is 2 seconds. The solver may take different internal steps.
The model definition identifies exp_dp (Real Expression), exp_m_flow (Real Expression). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Reading the two channels
At 180 seconds, mov1.P is 13,185.326 and mov2.P is 12,850.772. Subtracting the second channel from the first gives +334.554 W, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Reproducing the largest recorded change
Between the stored points at 78 and 80 seconds, mov1.P changes from 20,622.477 to 22,830.26. Subtracting the earlier reading gives +2,207.783 W. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | mov1.P (W) | mov2.P (W) |
|---|---|---|
0 | 0 | 0 |
50 | 2853.735 | 2853.735 |
78 | 20622.48 | 20622.48 |
80 | 22830.26 | 22830.26 |
100 | 22830.26 | 22830.26 |
150 | 18327.12 | 18327.12 |
200 | 13185.33 | 12850.77 |
Applying the result to an operating site
Electrical input, shaft power and hydraulic power are different quantities. Keep the efficiency boundary with the source curve. For a field comparison, use the same delivered duty and make explicit whether motor and drive losses are inside the measured boundary.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.