The modSetPoi.TZon trace covers 10 to 35 °C, a temperature span of 25 K. The first recorded maximum occurs at 21,600 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ModeAndSetPoints. The source file places it under Controls, OBC, ASHRAE, G36, AH Us, Single Zone, variable air volume, Set Points. We used the 101 stored values for modSetPoi.TZon over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name modSetPoi (Mode And Set Points), cooSetAdj (Sin), heaSetAdj (Sin), cooDemLimLev (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel modSetPoi.TCooSet starts at 303.15, ends at 303.15 and has a recorded range of 296.152 to 303.15 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 43,200 to 44,064 seconds. Subtracting 295.65 from 294.865 gives -0.7849 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | modSetPoi.TZon (K) | modSetPoi.TCooSet (source units) |
|---|---|---|
0 | 295.65 | 303.15 |
17280 | 307.5382 | 303.15 |
21600 | 308.15 | 303.15 |
34560 | 302.9973 | 298.101 |
43200 | 295.65 | 297.65 |
44064 | 294.8651 | 297.15 |
51840 | 288.3027 | 297.15 |
64800 | 283.15 | 298.15 |
69120 | 283.7618 | 303.15 |
86400 | 295.65 | 303.15 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.