The recorded mixBox.damOA.m_flow channel spans 0.3367 to 1.136 kg/s in this reference run. It starts at 0.4082 and ends at 0.422. The first recorded maximum occurs at 19.2 seconds and the first minimum at 60 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named MixingBoxMinimumFlow. The source file places it under Fluid, Actuators, Dampers. We used the 101 stored values for mixBox.damOA.m_flow over the interval 0 to 240 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name mixBox (Mixing Box Minimum Flow). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel mixBox.damOAMin.m_flow covers 0.1342 to 0.4056 kg/s. At 19.2 s, the primary value is 1.136 and the companion is 0.4056. Their signed difference is 0.7306 kg/s, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Mixing box minimum flow. The simulated mixBox.damOA.m_flow channel runs from 0.3367 to 1.136 kg/s over 240 seconds.
Mixing box minimum flow. The simulated mixBox.damOA.m_flow channel runs from 0.3367 to 1.136 kg/s over 240 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 240 seconds gives a net 122.24 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

mixBox.damOA.m_flow (kg/s)

mixBox.damOAMin.m_flow (kg/s)

0

0.4082483

0.1341641

2.4

0.6248293

0.2070014

19.2

1.136212

0.4056101

48

0.5258143

0.2141606

60

0.3366863

0.1405767

96

0.4219882

0.1404161

144

0.4219882

0.1404161

192

0.4219882

0.1404161

240

0.4219882

0.1404161

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.