The senTemSup.T trace covers 17.234 to 20 °C, a temperature span of 2.766 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named DynamicValidation. The source file places it under Fluid, Mass Exchangers, Membrane Based Enthalpy Exchangers. We used the 101 stored values for senTemSup.T over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.

The source declares nParallel = 184, n = 15, heightDuct = 0.00225, widthDuct = 0.305. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel T_Sup_exp.showNumber starts at 17.564, ends at 17.648 and has a recorded range of 17.564 to 18.656 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Membrane based enthalpy exchangers dynamic. The simulated senTemSup.T channel runs from 290.384 to 293.15 K over 7,200 seconds.
Membrane based enthalpy exchangers dynamic. The simulated senTemSup.T channel runs from 290.384 to 293.15 K over 7,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 72 seconds. Subtracting 293.15 from 290.384 gives -2.766 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTemSup.T (K)

T_Sup_exp.showNumber (source units)

0

293.15

17.564

72

290.3838

17.564

1440

290.6429

17.564

2880

290.6429

17.564

4320

291.3893

18.572

5760

290.6694

17.648

7200

290.6694

17.648

What to check on site

Record the physical quantity and its reference state before checking agreement. A sensor model can include a delay or mixing volume that an algebraic reference omits. Align both acquisition time and location before interpreting a difference as calibration error.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.