The conversion divides the extracted 15-bit ratio by 32,768 and multiplies by the reference resistor. Use 430 Ω as the explicitly assumed reference in this example. The answer here is resistance before the RTD temperature curve is applied. With 15-bit ratio code at 10,000, the worked result is 131.226 on the rtd resistance (ohms) scale.

The recorded quantity and the calculated result

Keep three columns in a commissioning export: the original 15-bit ratio code, the configuration used in the conversion and the resulting rtd resistance (ohms). Recompute the result for the lower, middle and upper worked points before interpreting a field difference. A change in range, units or representation can otherwise be mistaken for a change in the process.

Two points to check independently

Take the neighbouring worked points 8,000 and 10,000 on the input axis. The results are 104.98 and 131.226, giving a signed difference of 26.245. The table preserves the calculated values before display rounding. These are calculated examples under the stated assumptions. They are not readings from a ProSense installation.

MAX31865 RTD resistance ratio. 15-bit ratio code changes from 6,000 to 15,000 and the calculated RTD resistance (ohms) changes from 78.735 to 196.838.
MAX31865 RTD resistance ratio. 15-bit ratio code changes from 6,000 to 15,000 and the calculated RTD resistance (ohms) changes from 78.735 to 196.838. Figure by Industry Applied.

Worked data

15-bit ratio code

RTD resistance (ohms)

6000

78.73535

7600

99.73145

8000

104.9805

10000

131.2256

12000

157.4707

15000

196.8384

Checking the ends of the working range

The final interval in this example runs from 10,000 to 15,000 on the 15-bit ratio code axis. Its average change in rtd resistance (ohms) per input unit is 0.01312. This is a two-point slope for that interval. To check a spreadsheet or a gateway calculation, enter 15,000 in a separate test row and compare its result against 196.838 at the displayed precision.

Installation and interpretation

Record the actual reference resistor and the probe wiring arrangement. The device fault flag and a valid numerical ratio carry different information. Keep both before diagnosing a high apparent temperature.

For a repeatable verification, capture a small known case and a second case well away from it. Check whether the difference follows the response in the table, then restore the working configuration and repeat one reading. Store a separate status field for missing or invalid input. Substituting zero would make a dropped observation indistinguishable from a legitimate numerical zero.

Implementation and worked data

The source implementation is maintained in the .NET IoT device project. The component notes and manufacturer references document the supported device and its interfaces. Download the worked numerical example.