The recorded borHol.TBorAve temperature spans -6.104e-06 °C to 61.695 °C in this simulation. That is a change of 61.695 K. The first saved maximum occurs at 3.154e+10 s. The source trace and download retain absolute temperatures in kelvin.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ConstantHeatInjection_100Boreholes. The source file places it under Fluid, Geothermal, Borefields. We used the 101 stored values for borHol.TBorAve over the interval 0 to 31,536,001,024 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name borHol (One U Tube), pum (Flow Controlled m flow), TBorFieIn (Temperature Two Port), TBorFieOut (Temperature Two Port). The source declares T_start = 273.15. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The primary channel spends 98.0% of its saved checkpoints at or above 303.998 source units, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 331.506 source units. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 315,360,010 seconds. Subtracting 273.15 from 297.074 gives 23.924 source units. Its location brackets the change within one saved interval of 315,360,010 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | borHol.TBorAve (K) |
|---|---|
0 | 273.15 |
3.1536e+08 | 297.0737 |
6.3072e+09 | 331.0282 |
1.26144e+10 | 333.5269 |
1.89216e+10 | 334.2943 |
2.52288e+10 | 334.6483 |
3.1536e+10 | 334.8452 |
What to check on site
The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Units in the source model
The component declarations identify the scale of the exported variables. In this run, borHol.TBorAve uses K. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.