The senTCDU_a.T trace covers 20 to 41.545 °C, a temperature span of 21.545 K. The first recorded maximum occurs at 25,859,520 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ChillerWSE. The source file places it under Applications, Data Centers, Liquid Cooled. We used the 101 stored values for senTCDU_a.T over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name datRac (OCP 1k W OAM PG25), uti (Constant), rac (Cold Plate R P), bou (Boundary p T). The source declares PRac = 1E6, fraWSE = 0.6, dpHexChi_nominal = 80000, dPRac_nominal = 60000. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTCDU_b.T covers 293.15 to 320.604 K. At 3,784,320 s, the primary value is 314.695 and the companion is 320.604. Their signed difference is -5.909 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Liquid-cooled data centre with chiller and waterside economiser. The simulated senTCDU_a.T channel runs from 293.15 to 314.695 K over 31,536,000 seconds.
Liquid-cooled data centre with chiller and waterside economiser. The simulated senTCDU_a.T channel runs from 293.15 to 314.695 K over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 315,360 seconds. Subtracting 293.15 from 314.695 gives 21.545 K. Its location brackets the change within one saved interval of 315,360 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTCDU_a.T (K)

senTCDU_b.T (K)

0

293.15

293.15

315360

314.695

320.6036

6307200

314.6949

320.6036

1.26144e+07

314.6951

320.6035

1.89216e+07

314.6951

320.6035

2.52288e+07

314.6951

320.6035

2.585952e+07

314.6955

320.6034

3.1536e+07

314.695

320.6036

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.