The signed flow trace gives a net 44,742.6 kg over 5,000 s, using the trapezoidal rule between saved samples. The smallest and largest reported rates are 1.681e-05 kg/s and 23.901 kg/s. Check the positive flow direction in the model before using the sign to describe delivery or return.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ValvesIsolationPolyvalent. The source file places it under Templates, Plants, Heat Pumps, Components. We used the 101 stored values for valIsoCom.valChiWatUniInlIso[1].m_flow over the interval 0 to 5,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name valIsoCom (Valves Isolation), supChiWat (Boundary p T), supHeaWat (Boundary p T), ctl (Open Loop). The source declares nHp = 2, nPhp = 2. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 2,550 s, valIsoCom.valChiWatUniInlIso[1].m_flow is 1.681e-05 kg/s and valIsoCom.valChiWatUniInlIso[3].m_flow is 23.901 kg/s. Subtracting the second value from the first gives -23.901 kg/s. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.
![Isolation valve component with polyvalent heat pumps. The simulated valIsoCom.valChiWatUniInlIso[1].m_flow channel runs from 1.68e-05 to 23.901 kg/s over 5,000 seconds.](https://static.wixstatic.com/media/21e41b_431d10c679e1486ca52cf06ccc8de1b2~mv2.png/v1/fill/w_616,h_345,al_c,q_85,enc_auto/21e41b_431d10c679e1486ca52cf06ccc8de1b2~mv2.png)
Reproduce the calculation
Integrating the signed rate over 5,000 seconds gives a net 44,743 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | valIsoCom.valChiWatUniInlIso[1].m_flow (kg/s) | valIsoCom.valChiWatUniInlIso[3].m_flow (kg/s) |
|---|---|---|
0 | 0.0002688814 | 0 |
1000 | 0.0002688814 | 0 |
1150 | 1.680619e-05 | 0 |
2000 | 1.680619e-05 | 0 |
3000 | 1.680619e-05 | 23.90057 |
3100 | 0.0004672596 | 23.90057 |
3150 | 22.57682 | 23.90057 |
3250 | 23.90137 | 23.90057 |
4000 | 23.90137 | 23.90057 |
5000 | 23.90137 | 23.90057 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.


![Isolation valve component with polyvalent heat pumps. valIsoCom.valChiWatUniInlIso[1].m_flow (kg/s) ranges from 1.6806e−05 to 23.901 across the recorded simulation time (s) interval of 0 to 5,000. Bands show the minimum and maximum per group of samples. Crossbars mark the median.](/story-art/72af9748fbfcf73f8.webp)