The TSup1.T trace covers 5.56 to 20 °C, a temperature span of 14.44 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named IntegratedPrimarySecondary. The source file places it under Applications, Data Centers, Chiller Cooled, Equipment. We used the 101 stored values for TSup1.T over the interval 0 to 21,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name intWSEPriSec1 (Integrated Primary Secondary), yVal5 (Real Expression), yPum (Real Expression), sou2 (Boundary p T). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TSup2.T covers 278.71 to 293.15 K. At 3,672 s, the primary value is 285.43 and the companion is 285.097. Their signed difference is 0.3328 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Integrated primary secondary. The simulated TSup1.T channel runs from 278.71 to 293.15 K over 21,600 seconds.
Integrated primary secondary. The simulated TSup1.T channel runs from 278.71 to 293.15 K over 21,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 216 seconds. Subtracting 293.15 from 285.43 gives -7.72 K. Its location brackets the change within one saved interval of 216 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TSup1.T (K)

TSup2.T (K)

0

293.15

293.15

216

285.43

285.43

4320

285.43

285.43

7776

278.71

278.71

8640

278.71

278.71

12960

278.71

278.71

17280

281.3192

281.3192

21600

281.3192

281.3192

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.