The recorded hydraulicBus.TFwrdInMea temperature spans 29.877 °C to 50 °C in this simulation. That is a change of 20.123 K. The first saved maximum occurs at 480 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named Injection2WayValve. The source file places it under Systems, Hydraulic Modules. We used the 101 stored values for hydraulicBus.TFwrdInMea over the interval 0 to 800 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name hydRes (Pressure Drop). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 232 s, hydraulicBus.TFwrdInMea is 322.095 K and hydraulicBus.TFwrdOutMea is 304.074 K. Subtracting the second value from the first gives 18.021 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Injection circuit with a 2 way valve. The simulated hydraulicBus.TFwrdInMea channel runs from 303.027 to 323.15 source units over 800 seconds.
Injection circuit with a 2 way valve. The simulated hydraulicBus.TFwrdInMea channel runs from 303.027 to 323.15 source units over 800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 192 to 200 seconds. Subtracting 308.075 from 314.234 gives 6.159 source units. Its location brackets the change within one saved interval of 8 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hydraulicBus.TFwrdInMea (K)

hydraulicBus.TFwrdOutMea (K)

0

303.15

303.15

160

303.0395

303.3557

176

303.0274

303.3809

192

308.0753

303.4059

200

314.234

303.4221

320

323.147

314.5493

480

323.15

322.9751

640

323.15

323.1775

800

323.15

323.1753

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, hydraulicBus.TFwrdInMea uses K and hydraulicBus.TFwrdOutMea uses K. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.