The zon.T trace covers 20 to 24.495 °C, a temperature span of 4.495 K. The first recorded maximum occurs at 17,344,800 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named SimpleHouse. The source file places it under . We used the 101 stored values for zon.T over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name walCap (Heat Capacitor), zon (Mixing Volume), conRes (Thermal Resistor), rad (Radiator EN442 2). The source declares AWall = 100, AWin = 5, QHea_flow_nominal = 700, dpAir_nominal = 200. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TFanIn.T covers 288.32 to 298.511 K. At 630,720 s, the primary value is 294.84 and the companion is 288.332. Their signed difference is 6.508 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Illustrative of a simple heating, ventilation and room. The simulated zon.T channel runs from 293.15 to 297.645 K over 31,536,000 seconds.
Illustrative of a simple heating, ventilation and room. The simulated zon.T channel runs from 293.15 to 297.645 K over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 8,830,080 to 9,145,440 seconds. Subtracting 294.1 from 296.098 gives 1.998 K. Its location brackets the change within one saved interval of 315,360 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

zon.T (K)

TFanIn.T (K)

0

293.15

288.32

6307200

293.2027

290.1048

8830080

294.0996

291.9345

9145440

296.0981

296.4928

1.26144e+07

297.5253

295.279

1.73448e+07

297.6448

297.9756

1.89216e+07

297.5244

295.7882

2.52288e+07

294.4174

292.1422

3.1536e+07

293.2519

289.3891

What to check on site

Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.