The recorded ideUse1.dp channel spans 0 to 194,899 Pa in this reference run. It starts at 0 and ends at 60,284. The first recorded maximum occurs at 8,010 seconds and the first minimum at 0 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named StoragePlantDualSource. The source file places it under DHC, Plants, Cooling. We used the 101 stored values for ideUse1.dp over the interval 0 to 9,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name chi1 (Property Source T), TSet1 (Constant), pumSup1 (Speed Controlled y), conPI_pumChi1 (Lim PID). The source declares m_flow_nominal = 1, mTan_flow_nominal = 1, mChi_flow_nominal = 1. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel ideUse2.dp covers 0 to 172,449 Pa. At 2,250 s, the primary value is 60,000 and the companion is 93,321. Their signed difference is -33,321 Pa, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 8,820 to 8,910 seconds. Subtracting 194,899 from 71,486 gives -123,413 Pa. Its location brackets the change within one saved interval of 90 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | ideUse1.dp (Pa) | ideUse2.dp (Pa) |
|---|---|---|
0 | 0 | 0 |
1800 | 60044.39 | 60022.21 |
3600 | 58645.55 | 90241.08 |
5400 | 61285.63 | 92721.73 |
7200 | 60057.7 | 60505.44 |
8010 | 194898.6 | 172449.2 |
8820 | 194898.5 | 172449.2 |
8910 | 71485.83 | 68648.7 |
9000 | 60283.55 | 60261.28 |
What to check on site
Identify the stored quantity and the boundary through which energy or mass enters. A layer temperature, outlet temperature and volume mean describe different states. Preserve initial inventory and the sequence of charge or discharge when repeating the case.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.
Cover photograph by Daniel Dan, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.