The flo.eas.heaPorAir.Q_flow series gives a net -168.648 kWh over 432,000 s when the saved power samples are joined by straight lines. The highest recorded power is 3,357.2 W. The sign follows the model’s measurement boundary. It matters when a connector can exchange energy in either direction.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named IdealHeatingCoolingSummer_Autosizing. The source file places it under Thermal Zones, Energy Plus 24 2 0, Small Office. We used the 101 stored values for flo.eas.heaPorAir.Q_flow over the interval 16,848,000 to 17,280,000 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 22 recorded variables. Alongside the primary output there are flo.TAirCor, flo.TAirSou, flo.TAirNor, flo.TAirEas, flo.TAirWes. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

At 16,848,000 s, flo.eas.heaPorAir.Q_flow is 3,357.2 W and flo.nor.heaPorAir.Q_flow is 5,251.4 W. Subtracting the second value from the first gives -1,894.1 W. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Ideal heating cooling summer autosizing. The simulated flo.eas.heaPorAir.Q_flow channel runs from -3,187 to 3,357 W over 432,000 seconds.
Ideal heating cooling summer autosizing. The simulated flo.eas.heaPorAir.Q_flow channel runs from -3,187 to 3,357 W over 432,000 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed flo.eas.heaPorAir.Q_flow samples by the trapezoidal rule gives -168.648 kWh over 432,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

flo.eas.heaPorAir.Q_flow (W)

flo.nor.heaPorAir.Q_flow (W)

1.6848e+07

3357.22

5251.368

1.685232e+07

0

0

1.69344e+07

-541.7802

-723.6378

1.70208e+07

-756.498

-1047.667

1.71072e+07

-889.9904

-1342.722

1.71936e+07

-909.1181

-1374.433

1.724976e+07

-3187.473

-3153.141

1.728e+07

-839.9527

-1283.16

What to check on site

Identify the stored quantity and the boundary through which energy or mass enters. A layer temperature, outlet temperature and volume mean describe different states. Preserve initial inventory and the sequence of charge or discharge when repeating the case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.