The published iceTan.SOC signal spans 0 to 1 fraction of one in the reference run. It starts at 0.75 and finishes at 0.167. The signed change between those endpoint samples is -0.583 fraction of one.

What the reference test measures

The Buildings model named Tank comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 86,400 seconds. Industry Applied extracted 101 checkpoints for iceTan.SOC and kept the original signed values. The regular output spacing is 864 seconds. The solver may take different internal steps.

The model definition identifies iceTanUnc (Tank), res (Pressure Drop), resUnc (Pressure Drop). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares res.dp_nominal = 500, resUnc.dp_nominal = 500. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 79,488 seconds, iceTan.SOC is 0.045 and iceTanUnc.SOC is 0.26. Subtracting the second channel from the first gives -0.215 fraction of one, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Ice-storage state of charge. In the simulated Tank case, iceTan.SOC ranges from 0 to 1 fraction of one over 86,400 seconds.
Ice-storage state of charge. In the simulated Tank case, iceTan.SOC ranges from 0 to 1 fraction of one over 86,400 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 39,744 and 40,608 seconds, iceTan.SOC changes from 0.815 to 0.755. Subtracting the earlier reading gives -0.06 fraction of one. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

iceTan.SOC (fraction)

iceTanUnc.SOC (fraction)

0

0.75

0.75

21600

0.9359975

1

25920

1

1

39744

0.8150463

0.7166093

40608

0.7551764

0.6601534

43200

0.5887032

0.5074818

57888

0

0

64800

0

0

86400

0.1674303

0.3822203

Applying the result to an operating site

The stored fraction is an internal energy-state estimate. It is different from instantaneous cooling rate. A local storage assessment needs a defined full and empty reference plus heat metering across the complete charge and discharge cycle.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.

Cover photograph by Daniel Dan, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.