The TChiWatEcoEnt.T trace covers 11.28 to 21.599 °C, a temperature span of 10.319 K. The first recorded maximum occurs at 1,040 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ChillersToPrimaryPumpsParallel. The source file places it under Templates, Plants, Chillers, Components. We used the 101 stored values for TChiWatEcoEnt.T over the interval 0 to 2,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name rou (Chillers To Primary Pumps), outPumChiWatPri (Multiple To Single), pumChiWatPri (Multiple), yPumChiWatPri (Constant). The source declares nChi = 3, tau = 10. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TChiWatChiEnt1[1].T covers 280.15 to 293.229 K. At 1,800 s, the primary value is 285.818 and the companion is 280.15. Their signed difference is 5.668 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Hydronic interface between parallel chillers and primary pumps. The simulated TChiWatEcoEnt.T channel runs from 284.43 to 294.749 K over 2,000 seconds.
Hydronic interface between parallel chillers and primary pumps. The simulated TChiWatEcoEnt.T channel runs from 284.43 to 294.749 K over 2,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 1,040 to 1,060 seconds. Subtracting 294.749 from 291.266 gives -3.483 K. Its location brackets the change within one saved interval of 20 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TChiWatEcoEnt.T (K)

TChiWatChiEnt1[1].T (K)

0

293.15

293.15

400

293.15

293.15

800

293.15

293.15

1040

294.7491

293.229

1060

291.2656

291.4174

1200

284.8635

284.1947

1600

285.2436

281.6594

2000

284.4302

280.1502

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.