The senTLiq_a.T trace covers 25.171 to 42.063 °C, a temperature span of 16.892 K. The first recorded maximum occurs at 1,152 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named AirLiquidRearDoorHexActive. The source file places it under Fluid, Data Centers, Racks, Hybrid. We used the 101 stored values for senTLiq_a.T over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 10 recorded variables. Alongside the primary output there are utiLiq.y[1], utiAir.y, senTLiq_a.T, senTLiq_b.T, senTAir_a.T. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel senTLiq_b.T covers 293.15 to 322.224 K. At 0 s, the primary value is 303.15 and the companion is 293.15. Their signed difference is 10 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Hybrid liquid-cooled and air-cooled rack with active rear door heat exchanger. The simulated senTLiq_a.T channel runs from 298.321 to 315.213 K over 7,200 seconds.
Hybrid liquid-cooled and air-cooled rack with active rear door heat exchanger. The simulated senTLiq_a.T channel runs from 298.321 to 315.213 K over 7,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 1,008 to 1,080 seconds. Subtracting 307.945 from 315.189 gives 7.244 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTLiq_a.T (K)

senTLiq_b.T (K)

0

303.15

293.15

72

298.3207

298.3106

1008

307.9453

308.5635

1080

315.1889

317.2301

1152

315.2126

318.2568

1440

315.2126

321.8261

2880

315.196

322.15

4320

315.196

322.15

5760

315.1874

322.1621

7200

315.1812

322.1812

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.