Add both lead resistances and divide by an approximate Pt100 sensitivity of 0.385 ohm per degree near zero Celsius. In the worked example, Resistance of each lead of 0.5 Ω gives approximate temperature bias of 2.5974 °C.

Set up the field measurement

Measure the loop leads separately or check the probe with a resistance simulator at the sensor end. Temperature changes along a long lead can move its resistance. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 0.25 Ω the calculated approximate temperature bias is 1.2987 °C. At 0.5 Ω it is 2.5974 °C. Subtracting the first output from the second gives 1.2987 °C. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Approximate temperature bias (°C) plotted against resistance of each lead (ω). Across the example the output changes from 0.2597 to 5.195.
Approximate temperature bias (°C) plotted against resistance of each lead (ω). Across the example the output changes from 0.2597 to 5.195. Figure by Industry Applied.

Worked data

Resistance of each lead (Ω)

Approximate temperature bias (°C)

0.05

0.2597403

0.1

0.5194805

0.25

1.298701

0.5

2.597403

0.75

3.896104

1

5.194805

Checking the working range

At the two ends of the example, an input of 0.05 gives 0.2597 and an input of 1 gives 5.195. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

The linear approximation is local to the stated region. A fully calibrated conversion uses the sensor curve and the actual input configuration. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.