The Simulation_VF_in_m3h.y trace ranges from 1.104e-14 to 0.9445 across 101 saved checkpoints. It begins at 1.104e-14 and finishes at 0.00076723 after 4,320 s of test time. The reference export does not state a verified engineering unit for this value. Use its native scale when comparing another run of the same model.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named AHU2_Heater. The source file places it under Systems, Modular air handler. We used the 101 stored values for Simulation_VF_in_m3h.y over the interval 0 to 4,320 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name data (AHU2 Reheater Ramp Valve). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 3,672 s, Simulation_VF_in_m3h.y reads 0.023162 and combiTimeTable.y[9] reads 0.037. Across the run, the second channel ranges from 0 to 1. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.
Reproduce the calculation
The largest absolute change between consecutive stored points appears from 3,629 to 3,672 seconds. Subtracting 0.6699 from 0.02316 gives -0.6467 source units. Its location brackets the change within one saved interval of 43.2 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | Simulation_VF_in_m3h.y (source units) | combiTimeTable.y[9] (source units) |
|---|---|---|
0 | 0 | 0 |
864 | 0.003679172 | 0 |
1728 | 0.1392038 | 0.13 |
2592 | 0.7726368 | 0.76 |
2980.8 | 0.9444991 | 0.99 |
3456 | 0.9442132 | 0.993 |
3628.8 | 0.6698674 | 0.8972 |
3672 | 0.02316191 | 0.037 |
4320 | 0.0007672289 | 0 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.