The loaCoo.TRet trace covers 2.001 to 11.999 °C, a temperature span of 9.998 K. The first recorded maximum occurs at 1,120 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named LoadAverage. The source file places it under Templates, Plants, Controls, Staging Rotation. We used the 101 stored values for loaCoo.TRet over the interval 0 to 2,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name loaHea (Load Average), THeaWatSupSet (Constant), THeaWatRet (Sin), V_flow (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel loaHea.TRet covers 323.152 to 343.148 K. At 1,120 s, the primary value is 285.149 and the companion is 343.148. Their signed difference is -57.999 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 740 to 760 seconds. Subtracting 279.941 from 280.359 gives 0.4188 K. Its location brackets the change within one saved interval of 20 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | loaCoo.TRet (K) | loaHea.TRet (K) |
|---|---|---|
0 | 280.15 | 333.15 |
380 | 275.1511 | 323.1522 |
400 | 275.1774 | 323.2048 |
740 | 279.9406 | 332.7312 |
760 | 280.3594 | 333.5688 |
800 | 281.1895 | 335.2291 |
1120 | 285.1489 | 343.1478 |
1200 | 284.9053 | 342.6606 |
1600 | 278.1163 | 329.0826 |
2000 | 275.8199 | 324.4897 |
What to check on site
Record each condition, calculated request and issued output as separate tags. Keep timestamps and the sample or event rule with the export. A stable displayed value may be held by logic after the measured input has changed.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model