The recorded TChiWatLvg.T temperature spans 7 °C to 20 °C in this simulation. That is a change of 13 K. The first saved maximum occurs at 0 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named HeatRecoveryChiller. The source file places it under Templates, Plants, Heat Pumps, Components. We used the 101 stored values for TChiWatLvg.T over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name inlChiWat (Boundary p T), inlHeaWat (Boundary p T), outHeaWat (Boundary p T), outChiWat (Boundary p T). The source declares COP_nominal = 3.6. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 580 s, TChiWatLvg.T is 280.15 K and THeaWatLvg.T is 323.15 K. Subtracting the second value from the first gives -43 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Heat recovery chiller. The simulated TChiWatLvg.T channel runs from 280.15 to 293.15 K over 1,000 seconds.
Heat recovery chiller. The simulated TChiWatLvg.T channel runs from 280.15 to 293.15 K over 1,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 120 to 130 seconds. Subtracting 290.525 from 288.001 gives -2.524 K. Its location brackets the change within one saved interval of 10 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TChiWatLvg.T (K)

THeaWatLvg.T (K)

0

293.15

293.15

120

290.5249

298.5139

130

288.0009

304.3486

200

280.9113

321.0247

400

280.151

323.1456

540

280.15

323.15

600

280.15

323.15

800

280.15

323.15

1000

282.0118

320.1725

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.