The vol.T trace covers 17.739 to 21.577 °C, a temperature span of 3.838 K. The first recorded maximum occurs at 131,328 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ScrollWaterToWater_OneRoomRadiator. The source file places it under Fluid, Heat Pumps. We used the 101 stored values for vol.T over the interval 0 to 172,800 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name theCon (Thermal Conductor), preHea (Prescribed Heat Flow), heaCap (Heat Capacitor), rad (Radiator EN442 2). The source declares Q_flow_nominal = 20000, TRadSup_nominal = 273.15 + 50, TRadRet_nominal = 273.15 + 45, V = 6*10*3. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel temRet.T covers 298.062 to 323.15 K. At 0 s, the primary value is 293.15 and the companion is 323.15. Their signed difference is -30 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Heat pump with scroll compressor connected to a simple room model with radiator. The simulated vol.T channel runs from 290.889 to 294.727 K over 172,800 seconds.
Heat pump with scroll compressor connected to a simple room model with radiator. The simulated vol.T channel runs from 290.889 to 294.727 K over 172,800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 27,648 to 29,376 seconds. Subtracting 291.279 from 294.45 gives 3.171 K. Its location brackets the change within one saved interval of 1,728 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

vol.T (K)

temRet.T (K)

0

293.15

323.15

1728

290.8893

311.0986

27648

291.2794

308.6849

29376

294.4502

312.9949

34560

291.9617

306.1996

69120

293.6763

312.1187

103680

291.7162

305.4333

131328

294.7274

306.6987

138240

294.3504

307.6551

172800

294.0417

311.0558

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.