The recorded TRet[1].T temperature spans 7.0087 °C to 49.981 °C in this simulation. That is a change of 42.972 K. The first saved maximum occurs at 10,502,240 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named HeatPumpGroupAirToWater. The source file places it under Templates, Plants, Heat Pumps, Components. We used the 101 stored values for TRet[1].T over the interval 10,497,600 to 10,505,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sup (Boundary p T), inlHp1 (Boundary p T), ctlPlaAwNrv (Open Loop), hpAwNrv (Air To Water). The source declares nHp = 3. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 10,501,680 s, TRet[1].T is 307.933 K and TSup[1].T is 322.521 K. Subtracting the second value from the first gives -14.588 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Heat pump group with awhp. The simulated TRet[1].T channel runs from 280.159 to 323.131 K over 8,000 seconds.
Heat pump group with awhp. The simulated TRet[1].T channel runs from 280.159 to 323.131 K over 8,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 10,500,000 to 10,500,080 seconds. Subtracting 285.13 from 318.96 gives 33.829 K. Its location brackets the change within one saved interval of 80 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TRet[1].T (K)

TSup[1].T (K)

1.04976e+07

293.15

293.15

1.04992e+07

289.8991

283.6654

1.049976e+07

280.1587

280.15

1.05e+07

285.1304

280.15

1.050008e+07

318.9598

315.1376

1.05008e+07

307.5263

307.3467

1.050224e+07

323.1308

323.15

1.05024e+07

319.8928

323.15

1.0504e+07

285.1304

280.15

1.05056e+07

310.4886

311.832

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.