The published heaPum.COP signal spans 1.964 to 3.019 ratio in the reference run. It starts at 3.019 and finishes at 1.964. The signed change between those endpoint samples is -1.055 ratio.

What the reference test measures

The Buildings model named Carnot_TCon comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 3,600 seconds. Industry Applied extracted 101 checkpoints for heaPum.COP and kept the original signed values. The regular output spacing is 36 seconds. The solver may take different internal steps.

The model definition identifies heaPum (Carnot T Con), TConLvg (Ramp), mEva_flow (Gain). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares TConLvg.duration = 60, TConLvg.startTime = 1800, TConLvg.height = 15. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

The companion channel heaPum.P spans 49,489.758 to 152,159.891 W across its 101 stored values. The primary trace first reaches its recorded maximum at 0 seconds and its minimum at 1,872 seconds. A time-aligned comparison preserves the meaning and units of each channel.

Heat-pump coefficient of performance. In the simulated Carnot_TCon case, heaPum.COP ranges from 1.964 to 3.019 ratio over 3,600 seconds.
Heat-pump coefficient of performance. In the simulated Carnot_TCon case, heaPum.COP ranges from 1.964 to 3.019 ratio over 3,600 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 1,800 and 1,836 seconds, heaPum.COP changes from 3.019 to 2.262. Subtracting the earlier reading gives -0.757 ratio. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

heaPum.COP (ratio)

heaPum.P (W)

0

3.019384

49489.76

900

3.019384

49489.76

1800

3.019384

49489.76

1836

2.262497

105673.4

1872

1.964099

152159.9

2700

1.964099

152159.9

3600

1.964099

152159.9

Applying the result to an operating site

COP is useful heat divided by electrical input within a declared boundary. It depends on source and sink conditions and can be unrepresentative at very low input. An energy-weighted period COP requires totals of heat and electricity over the same interval.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.