The recorded heaPum.QEva_flow channel spans -134,545 to 0 W in this reference run. It starts at -134,545 and ends at 0. The first recorded maximum occurs at 1,872 seconds and the first minimum at 0 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named Carnot_y_etaCar. The source file places it under Fluid, Heat Pumps. We used the 101 stored values for heaPum.QEva_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.
The reference file contains 11 recorded variables. Alongside the primary output there are heaPum.sta_a1.T, heaPum.sta_b1.T, heaPum.sta_a2.T, heaPum.sta_b2.T, heaPum.QEva_flow. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.
Compare the recorded channels
The companion channel heaPum.QCon_flow covers 0 to 144,545 W. At 0 s, the primary value is -134,545 and the companion is 144,545. Their signed difference is -279,091 W, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
Integrating the signed heaPum.QEva_flow samples by the trapezoidal rule gives -22.059 kWh over 3,600 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | heaPum.QEva_flow (W) | heaPum.QCon_flow (W) |
|---|---|---|
0 | -134545.3 | 144545.3 |
36 | -60907.26 | 70907.26 |
720 | -36665.93 | 46665.93 |
1440 | -46586.11 | 56586.11 |
1872 | 0 | 0 |
2160 | 0 | 0 |
2880 | 0 | 0 |
3600 | 0 | 0 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.