The published con.port_a.Q_flow signal spans 0 to 92.379 W in the reference run. It starts at 0 and finishes at 92.379. The signed change between those endpoint samples is +92.379 W.

What the reference test measures

The Buildings model named ConductorStepResponse comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 86,400 seconds. Industry Applied extracted 101 checkpoints for con.port_a.Q_flow and kept the original signed values. The regular output spacing is 864 seconds. The solver may take different internal steps.

The model definition identifies cheEqu (Add), conv1 (Interior), conv2 (Interior). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Reading the two channels

At 84,672 seconds, con.port_a.Q_flow is 92.379 and con1.port_a.Q_flow is 31.469. Subtracting the second channel from the first gives +60.91 W, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Heat flux response to a boundary step. In the simulated ConductorStepResponse case, con.port_a.Q_flow ranges from 0 to 92.379 W over 86,400 seconds.
Heat flux response to a boundary step. In the simulated ConductorStepResponse case, con.port_a.Q_flow ranges from 0 to 92.379 W over 86,400 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 3,456 and 4,320 seconds, con.port_a.Q_flow changes from 0 to 92.379. Subtracting the earlier reading gives +92.379 W. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

con.port_a.Q_flow (W)

con1.port_a.Q_flow (W)

0

0

0

3456

0

0

4320

92.37875

34.64756

21600

92.37875

31.77586

43200

92.37875

31.4854

64800

92.37875

31.47059

86400

92.37875

31.46892

Applying the result to an operating site

A transient step tests how quickly a material takes up heat. A coarse output interval can miss a short initial peak. Keep the applied boundary condition and the first recorded point visible when comparing different instruments or model discretisations.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.