The published con.port_a.Q_flow signal spans 0 to 475.619 W in the reference run. It starts at 0 and finishes at 148.333. The signed change between those endpoint samples is +148.333 W.

What the reference test measures

The Buildings model named ConductorSteadyStateTransient comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 86,400 seconds. Industry Applied extracted 101 checkpoints for con.port_a.Q_flow and kept the original signed values. The regular output spacing is 864 seconds. The solver may take different internal steps.

The model definition identifies cheEqu (Add), conv1 (Interior), conv2 (Interior). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Reading the two channels

At 4,320 seconds, con.port_a.Q_flow is 475.619 and con1.port_a.Q_flow is 9.798. Subtracting the second channel from the first gives +465.821 W, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Heat flow at a conductor boundary. In the simulated ConductorSteadyStateTransient case, con.port_a.Q_flow ranges from 0 to 475.619 W over 86,400 seconds.
Heat flow at a conductor boundary. In the simulated ConductorSteadyStateTransient case, con.port_a.Q_flow ranges from 0 to 475.619 W over 86,400 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 3,456 and 4,320 seconds, con.port_a.Q_flow changes from 0 to 475.619. Subtracting the earlier reading gives +475.619 W. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

con.port_a.Q_flow (W)

con1.port_a.Q_flow (W)

0

0

0

3456

0

0

4320

475.6193

9.798145

21600

149.1701

9.442959

43200

148.3377

9.37711

64800

148.3331

9.369555

86400

148.3333

9.368539

Applying the result to an operating site

Heat entering a wall can be stored before a matching flow leaves the far side. Record both boundary directions and the thermal storage term. A steady resistance calculation and a short-time heat-flux reading need not agree during a transient.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.