The hex.sta_a1.T trace covers 5 to 35 °C, a temperature span of 30 K. The first recorded maximum occurs at 2,304 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named DryCoilCounterFlowPControl. The source file places it under Fluid, Heat Exchangers. We used the 101 stored values for hex.sta_a1.T over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name val (Two Way Equal Percentage), con (Lim PID), TWat (Ramp). The source declares m1_flow_nominal = 0.1. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel hex.sta_b1.T covers 282.771 to 307.226 K. At 0 s, the primary value is 278.15 and the companion is 293.15. Their signed difference is -15 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Heat exchanger without condensation and with feedback control. The simulated hex.sta_a1.T channel runs from 278.15 to 308.15 K over 3,600 seconds.
Heat exchanger without condensation and with feedback control. The simulated hex.sta_a1.T channel runs from 278.15 to 308.15 K over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 792 to 828 seconds. Subtracting 285.53 from 286.07 gives 0.54 K. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hex.sta_a1.T (K)

hex.sta_b1.T (K)

0

278.15

293.15

720

284.45

292.2299

792

285.53

292.821

828

286.07

293.0391

1440

295.25

296.5806

2160

306.05

305.3844

2304

308.15

307.1441

2880

308.15

307.2258

3600

308.15

307.2258

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.