The recorded frePro.uCooCoi channel spans 0.5 to 0.7 source units in this reference run. It starts at 0.5 and ends at 0.7. The first recorded maximum occurs at 3,600 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named FreezeProtection_Disable. The source file places it under Controls, OBC, ASHRAE, G36, AH Us, Multi Zone, variable air volume, Set Points. We used the 101 stored values for frePro.uCooCoi over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name frePro (Freeze Protection), outDamPos (Ramp), heaCoiPos (Ramp), minOutDamPos (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The two named channels have separate paths in the model. frePro.uCooCoi begins at 0.5 and ends at 0.7. frePro.uHeaCoi begins at 0.5 and ends at 0.96. The reference export supplies numerical samples but does not attach a physical unit to these fields. Use the linked model declarations to establish the quantity and units of each channel before calculating a difference or assigning it a physical meaning.

Freeze protection disable. The simulated frePro.uCooCoi channel runs from 0.5 to 0.7 source units over 3,600 seconds.
Freeze protection disable. The simulated frePro.uCooCoi channel runs from 0.5 to 0.7 source units over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 36 to 72 seconds. Subtracting 0.502 from 0.504 gives 0.002 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

frePro.uCooCoi (source units)

frePro.uHeaCoi (source units)

0

0.5

0.5

36

0.502

0.5046

72

0.504

0.5092

720

0.54

0.592

1440

0.58

0.684

2160

0.62

0.776

2880

0.66

0.868

3600

0.7

0.96

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.