The volA.T trace covers 18 to 20.717 °C, a temperature span of 2.717 K. The first recorded maximum occurs at 3,600 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named NaturalVentilation. The source file places it under Airflow, Multizone. We used the 101 stored values for volA.T over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name volA (Mixing Volume), oriOutBot (Orifice), colOut (Medium Column), oriOutTop (Orifice). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel oriOutBot.v starts at 0, ends at -0.1117 and has a recorded range of -0.1548 to 0.2859 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Flow reversal due to density difference. The simulated volA.T channel runs from 291.15 to 293.867 K over 7,200 seconds.
Flow reversal due to density difference. The simulated volA.T channel runs from 291.15 to 293.867 K over 7,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 72 seconds. Subtracting 291.15 from 291.23 gives 0.07999 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

volA.T (K)

oriOutBot.v (source units)

0

291.15

0

72

291.23

0.2858878

1440

292.4556

0.1514622

2880

293.4283

-0.06542542

3600

293.8668

-0.1548262

4320

293.8077

-0.1442285

5760

293.713

-0.1262222

7200

293.6411

-0.1117288

What to check on site

Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.