The published pumFixDp.m_flow signal spans -0.494 to 0.972 kg/s in the reference run. It starts at 0.972 and finishes at -0.494. The signed change between those endpoint samples is -1.466 kg/s.
What the reference test measures
The Buildings model named SpeedControlled_y_linear comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 1 seconds. Industry Applied extracted 101 checkpoints for pumFixDp.m_flow and kept the original signed values. The regular output spacing is 0.01 seconds. The solver may take different internal steps.
The model definition identifies pumFixDp (Speed Controlled y), pumFixM_flow (Speed Controlled y), y (Ramp). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Settings to preserve when repeating the experiment
The published test declares y.offset = 1, y.duration = 0.5, y.startTime = 0.25. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
The companion channel pumFixM_flow.dp spans -19,899.557 to 0.025 Pa across its 101 stored values. The primary trace first reaches its recorded maximum at 0 seconds and its minimum at 0.75 seconds. A time-aligned comparison preserves the meaning and units of each channel.

Reproducing the largest recorded change
Between the stored points at 0.74 and 0.75 seconds, pumFixDp.m_flow changes from -0.243 to -0.494. Subtracting the earlier reading gives -0.251 kg/s. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | pumFixDp.m_flow (kg/s) | pumFixM_flow.dp (Pa) |
|---|---|---|
0 | 0.9718034 | -19899.56 |
0.25 | 0.9718034 | -19899.56 |
0.5 | 0.4785958 | -4949.766 |
0.74 | -0.2426747 | -6.589824 |
0.75 | -0.4937617 | 0.02511084 |
1 | -0.4937617 | 0.02511084 |
Applying the result to an operating site
A pressure-controlled loop and a flow-controlled loop can produce different operating trajectories from the same speed command. Identify which variable is held fixed in each model branch. A bench curve should be compared at the same constraint.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.