The recorded conFCU1.TSup temperature spans 11.522 °C to 24.353 °C in this simulation. That is a change of 12.831 K. The first saved maximum occurs at 48,384 s. The source trace and download retain absolute temperatures in kelvin.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named FourPipe. The source file places it under Fan Coils. We used the 101 stored values for conFCU1.TSup over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name souHea (Boundary p T), sinHea (Boundary p T), sinCoo (Boundary p T), souCoo (Boundary p T). The source declares wSou = 49.91, wNor = 40.76, wSid = 6.47, hRoo = 2.74. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 54,432 s, conFCU1.TSup is 284.718 K and conFCU1.TZon is 297.18 K. Subtracting the second value from the first gives -12.462 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 66,528 to 67,392 seconds. Subtracting 288.317 from 293.396 gives 5.079 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | conFCU1.TSup (K) | conFCU1.TZon (K) |
|---|---|---|
0 | 293.15 | 293.15 |
17280 | 293.15 | 291.4757 |
34560 | 294.8906 | 294.9063 |
48384 | 297.5031 | 297.5247 |
51840 | 288.7831 | 297.2869 |
53568 | 284.6721 | 297.1137 |
66528 | 288.317 | 296.7191 |
67392 | 293.3957 | 296.45 |
69120 | 296.084 | 295.7056 |
86400 | 296.084 | 294.5902 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.