The hex.sta_a1.T trace covers 60 to 65 °C, a temperature span of 5 K. The first recorded maximum occurs at 122.4 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named DryCoilDiscretized. The source file places it under Fluid, Heat Exchangers. We used the 101 stored values for hex.sta_a1.T over the interval 0 to 360 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name TWat (Ramp), TDb (Constant), m_flow_2 (Ramp). The source declares m1_flow_nominal = 5. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel hex.sta_b1.T covers 293.11 to 334.195 K. At 7.2 s, the primary value is 333.15 and the companion is 293.11. Their signed difference is 40.04 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Finite volume model of a heat exchanger without condensation. The simulated hex.sta_a1.T channel runs from 333.15 to 338.15 K over 360 seconds.
Finite volume model of a heat exchanger without condensation. The simulated hex.sta_a1.T channel runs from 333.15 to 338.15 K over 360 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 64.8 to 68.4 seconds. Subtracting 333.55 from 333.85 gives 0.3 K. Its location brackets the change within one saved interval of 3.6 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hex.sta_a1.T (K)

hex.sta_b1.T (K)

0

333.15

293.15

64.8

333.55

310.4707

68.4

333.85

311.1982

72

334.15

311.8318

122.4

338.15

316.2004

144

338.15

317.5747

216

338.15

326.8185

288

338.15

334.0838

360

338.15

334.0103

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.